Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2021, 10:42 AM
  • 05 0506_05 0505_01272021_025640.mp4

Date
01/27/2021
W/O
870604
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00459
PipeID
P05723
Time
2:42 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8510
Sewer Name
05 INGLEWOOD TRUNK #1
City
INGELWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_870604_TV05042_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
05 0506
Downstream MH
05 0505
Dir. of Survey
Downstream
Length Surveyed
196.4 ft.
Total Length
196.4 ft.
Structural Index
2
Structural Quick
2G00
Structural Rating
76
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
152
Pipe schematic from manhole 05 0506 to 05 0505
MH: 05 0506MH: 05 0505downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 05062 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4" - OPEN63.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4" - OPEN115.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4" - OPEN167.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4" - OPEN194 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish196.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0505

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
23.5TFOPEN
0MWM
115.9TFOPEN
0MWL
194SSS
0AMH05 0506
167.9TFOPEN
63.6TFOPEN
194.7DAGS
196.4AMH05 0505
2SSS
4.3DAGS

Properties (8)

additional_info
SC411898
custom_field_three
GREASE
custom_field_two
4
customer
1
datetime
2021-01-27T02:42:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP