Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2021, 07:45 AM
  • 22 0272A_22 0272_02032021_235741.mp4

Date
02/03/2021
W/O
870562
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00793
PipeID
P16558
Time
11:45 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8390
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_870562_TV22016_JAN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0272
Downstream MH
22 0272A
Dir. of Survey
Upstream
Length Surveyed
165.8 ft.
Total Length
165.8 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 22 0272 to 22 0272A
MH: 22 0272MH: 22 0272Aupstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 22 0272A0.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"54.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.9 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish80.4 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start85.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"109.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"125.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"137.5 ft. LR - Alignment Right, 20 %, Finish162.7 ft. LR - Alignment Right, 20 %, Start162.7 ft. MGO - General Observation - MAG COAT162.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start162.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.8 ft. AMH - Downstream Manhole, Survey Begins - 22 0272165.8 ft. MWL - Water Level, 20 %of cross sectional area165.8 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (6)

  • Alignment Right, 20 %, Start

    3.1 ft. - Alignment Right, 20 %, Start

  • General Observation - MAG COAT

    3.1 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    85.4 ft. - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    111.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
165.8SAP
85.4SRP
165.8SSS
165.5SRV
3.1LR
165.8MGOCONNECTION AT MH 9 O'CLOCK
159.3TFC
3.1MGOMAG COAT
28.3LR
56.4TFC
80.7TFC
97.9SRP
3.1SSS
0AMH22 0272
40.7TF
111.6SRV
165.8AMH22 0272A
0MWL
0MWM
3.1SAP

Properties (6)

custom_field_three
AGGREGATE PROJECTING, REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-02-03T23:45:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false