Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2021, 09:56 AM
  • 03 0346_03 0345_02112021_024534.mp4

Date
02/11/2021
W/O
870241
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00369
PipeID
P04920
Time
1:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8478
Sewer Name
03 MARINA TRUNK, SECTION 1A
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
WO_870241_TV03172_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
30 in.
Upstream MH
03 0346
Downstream MH
03 0345
Dir. of Survey
Downstream
Length Surveyed
276.9 ft.
Total Length
276.9 ft.
Structural Index
2
Structural Quick
322T
Structural Rating
214
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
322
Pipe schematic from manhole 03 0346 to 03 0345
MH: 03 0346MH: 03 0345downstream0 ft. MGO - General Observation - CONN@ MH 3 O'CLOCK/OPEN0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 03462 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start274 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish274 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish274 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish274 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish276.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0345

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
25MWLS
0MGOCONN@ MH 3 O'CLOCK/OPEN
2DAGS
0MWM
0MWL
274DAGS
2SSS
276.9AMH03 0345
274CM
274MWLS
0AMH03 0346
274SSS
2CM

Properties (7)

additional_info
630074021021206
custom_field_three
/MULTIPLE CRACKS/SPALLING
custom_field_two
3
customer
1
datetime
2021-02-11T01:56:32-08:00
documentation
PROPIPE
is_lateral_inspection
false