Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2021, 12:39 PM
  • 01 0354_01 0353_02012021_045218.mp4

Date
02/01/2021
W/O
870425
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00215
PipeID
P00828
Time
4:39 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8449
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_870425_TV01077_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0354
Downstream MH
01 0353
Dir. of Survey
Downstream
Length Surveyed
341 ft.
Total Length
341 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
145
Pipe schematic from manhole 01 0354 to 01 0353
MH: 01 0354MH: 01 0353downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03542 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start96.5 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES137.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES273.8 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES339.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE339.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish341 ft. AMH - Downstream Manhole, Survey Ends - 01 0353

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    96.5 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    137.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    273.8 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    339.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
341AMH01 0353
339.5MGOCOCKROACHES IN MANHOLE
0MWM
2DAGS
137.1FM
0MWL
339.5DAGS
273.8FM
0AMH02 0354
96.5CM

Properties (7)

additional_info
630969020121002
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-02-01T04:39:20-08:00
documentation
PRO PIPE
is_lateral_inspection
false