Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 15, 2021, 08:54 AM
  • C 0487_C 0486_02152021_012456.mp4

Date
02/15/2021
W/O
870532
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00132
PipeID
P09737
Time
12:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8481
Sewer Name
C JOINT OUTFALL C - UNIT 6C RENOVATION*
City
lakewood
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_870532_TV03155_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
24 in.
Upstream MH
C 0487
Downstream MH
C 0486
Dir. of Survey
Downstream
Length Surveyed
63.3 ft.
Total Length
63.3 ft.
Structural Index
3
Structural Quick
3600
Structural Rating
18
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole C 0487 to C 0486
MH: C 0487MH: C 0486downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 04870 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start6.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish63.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish63.3 ft. AMH - Downstream Manhole, Survey Ends - C 0486

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.1DAGS
0MWL
0AMHC 0487
6.4CM
63.3DAGS
0MWM
63.3AMHC 0486
35.7CM

Properties (8)

additional_info
630074021521001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-02-15T00:54:03-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
33064