Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2021, 06:32 AM
  • A 0851_A 0850_02162021_223736.mp4

Date
02/16/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08191
Time
10:32 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8485
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
14 in.
Upstream MH
A 0851
Downstream MH
A 0850
Dir. of Survey
Downstream
Length Surveyed
104.5 ft.
Total Length
104.5 ft.
Structural Index
2
Structural Quick
2C11
Structural Rating
41
O&M Index
2
O&M Quick
2C00
O&M Rating
40
Overall Index
2
Overall Quick
Overall Rating
81
Pipe schematic from manhole A 0851 to A 0850
MH: A 0851MH: A 0850downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - A 08510.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0.3 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES102 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish102 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish104.5 ft. AMH - Downstream Manhole, Survey Ends - A 0850

Observation photos (1)

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    97 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0.1MGOCONNECTION AT THE MH 3 OC'LOCK
0.3MWM
102DAGS
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
104.5AMHA 0850
97CC
2DAGS
102SSS
0AMHA 0851
2SSS

Properties (7)

additional_info
630074021621201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-02-16T22:32:43-08:00
documentation
PROPIPE
is_lateral_inspection
false