Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2021, 07:41 AM
  • A 0849_A 0848_02022021_001057.mp4

Date
02/01/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08189
Time
11:41 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8463
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
14 in.
Upstream MH
A 0849
Downstream MH
A 0848
Dir. of Survey
Downstream
Length Surveyed
742.4 ft.
Total Length
742.4 ft.
Structural Index
2
Structural Quick
312]
Structural Rating
300
O&M Index
2
O&M Quick
2]11
O&M Rating
299
Overall Index
2
Overall Quick
Overall Rating
599
Pipe schematic from manhole A 0849 to A 0848
MH: A 0849MH: A 0848downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08492 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES481.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES596 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES596.3 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES740 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish740 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish742.4 ft. AMH - Downstream Manhole, Survey Ends - A 0848

Observation photos (2)

  • Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    3.2 ft. - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    481.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
740SSS
0MWM
596DAE
596.3RFJ
740DAGS
2DAGS
742.4AMHA 0848
0MWL
3.2CC
0AMHA 0849
2SSS
481.8CM

Properties (7)

additional_info
630074020121201
custom_field_three
spalling
custom_field_two
3
customer
1
datetime
2021-02-01T23:41:10-08:00
documentation
PROPIPE
is_lateral_inspection
false