Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2021, 11:35 AM
  • A 0844_A 0843_02022021_040412.mp4

Date
02/02/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08184
Time
3:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8463
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
A 0844
Downstream MH
A 0843
Dir. of Survey
Downstream
Length Surveyed
815.5 ft.
Total Length
815.5 ft.
Structural Index
2
Structural Quick
2_00
Structural Rating
324
O&M Index
2
O&M Quick
2`00
O&M Rating
326
Overall Index
2
Overall Quick
Overall Rating
650
Pipe schematic from manhole A 0844 to A 0843
MH: A 0844MH: A 0843downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08440 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start732.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES813 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish813 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish815.5 ft. AMH - Downstream Manhole, Survey Ends - A 0843 (ZOOMED)

Observations (9)

DistanceCodeObservation
813SSS
813DAGS
815.5AMHA 0843 (ZOOMED)
2SSS
0MWM
0AMHA 0844
0MWL
732.2DAE
2DAGS

Properties (7)

additional_info
630074020121201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-02-02T03:35:28-08:00
documentation
PROPIPE
is_lateral_inspection
false