Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2021, 10:07 AM
  • A 0837_A 0836_02032021_022434.mp4

Date
02/03/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08177
Time
2:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8464
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
39 in.
Upstream MH
A 0837
Downstream MH
A 0836
Dir. of Survey
Downstream
Length Surveyed
418.7 ft.
Total Length
418.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole A 0837 to A 0836
MH: A 0837MH: A 0836downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 083728.2 ft. MMC - Material Change, Reinforced concrete pipe28.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.5 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: YES, 4", 6"30.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"31.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish32 ft. MMC - Material Change, Vitrified clay pipe418.7 ft. AMH - Downstream Manhole, Survey Ends - A 0836

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Vitrified clay pipe

    32 ft. - Material Change, Vitrified clay pipe

Observations (10)

DistanceCodeObservation
28.2MMC
31.2SAP
28.2SAP
0MWM
0MWL
29.5TFB
32MMC
418.7AMHA 0836
0AMHA 0837
30.2TFA

Properties (7)

additional_info
630074020221201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-02-03T02:07:06-08:00
documentation
PROPIPE
is_lateral_inspection
false