Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2021, 05:18 AM
  • A 0834_A 0833_02032021_214137.mp4

Date
02/03/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08174
Time
9:18 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8465
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
39 in.
Upstream MH
A 0834
Downstream MH
A 0833
Dir. of Survey
Downstream
Length Surveyed
557 ft.
Total Length
557 ft.
Structural Index
2
Structural Quick
2U00
Structural Rating
220
O&M Index
2
O&M Quick
2U00
O&M Rating
220
Overall Index
2
Overall Quick
Overall Rating
440
Pipe schematic from manhole A 0834 to A 0833
MH: A 0834MH: A 0833downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08340 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start554 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish554 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish557 ft. AMH - Downstream Manhole, Survey Ends - A 0833

Observations (10)

DistanceCodeObservation
554SSS
2DAGS
0MWM
0MWL
2SSS
0AMHA 0834
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
557AMHA 0833
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
554DAGS

Properties (7)

additional_info
630074020321201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-02-03T21:18:41-08:00
documentation
PROPIPE
is_lateral_inspection
false