Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2021, 11:42 AM
  • A 0853_A 0852_02042021_035312.mp4

Date
02/04/2021
W/O
870569
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00324
PipeID
P08193
Time
3:42 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8465
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
WO_870569_TV03038_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
14 in.
Upstream MH
A 0853
Downstream MH
A 0852
Dir. of Survey
Downstream
Length Surveyed
106.2 ft.
Total Length
106.2 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
40
O&M Index
2
O&M Quick
312C
O&M Rating
43
Overall Index
2
Overall Quick
Overall Rating
83
Pipe schematic from manhole A 0853 to A 0852
MH: A 0853MH: A 0852downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08530 ft. MGO - General Observation - CONNECTION AT THE MH 6 OC'LOCK0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start104 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish104 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish106.2 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - SLUDGE/DEBRIS106.2 ft. MSA - Survey Abandoned - CAM BLKD BY DEBRIS

Observation photos (1)

  • Deposits Settled Other,  20 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - SLUDGE/DEBRIS

    106.2 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - SLUDGE/DEBRIS

Observations (10)

DistanceCodeObservation
2DAGS
0MWM
104DAGS
0AMHA 0853
2SSS
0MGOCONNECTION AT THE MH 6 OC'LOCK
104SSS
106.2DSZSLUDGE/DEBRIS
0MWL
106.2MSACAM BLKD BY DEBRIS

Properties (6)

additional_info
630074020321201
custom_field_two
5
customer
1
datetime
2021-02-04T03:42:25-08:00
documentation
PROPIPE
is_lateral_inspection
false