Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 09:29 AM
  • B 0605_B 0604_3122021_042024.mp4

Date
03/12/2021
W/O
0875029
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00105
PipeID
P09177
Time
1:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1748
Sewer Name
B JOINT OUTFALL B - UNIT 8B
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
20210312MDM_JOINT_OUTFALL_B_UNIT_8B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
B 0605
Downstream MH
B 0604
Dir. of Survey
Downstream
Length Surveyed
177.2 ft.
Total Length
177.2 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole B 0605 to B 0604
MH: B 0605MH: B 0604downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 100% START25.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open120.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT141.9 ft. MGO - General Observation - 100% MAG COAT176.7 ft. MGO - General Observation - MAG COAT 100% FINISH176.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT176.7 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN177.2 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 100% START

    2 ft. - General Observation - MAG COAT 100% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

    120.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

  • General Observation - 100% MAG COAT

    141.9 ft. - General Observation - 100% MAG COAT

Observations (14)

DistanceCodeObservation
0AMH4:20AM
0MWM
176.7MGOMAG COAT 100% FINISH
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MGOConn. @ Mh, 9 O' Clock. Active
176.7SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
120.9SSSBLISTERING CONCRETE UNDER MAG COAT
2MGOMAG COAT 100% START
141.9MGO100% MAG COAT
25.7TFOpen
0MGOConn. @ Mh, 3 O' Clock. OPEN
176.7MGOConn. @ Mh, 9 O' Clock. OPEN
177.2AMH4:30AM
0MWL

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE UNDER 100% MAG COAT
custom_field_two
4
customer
LACSD
datetime
2021-03-12T01:29:10-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA