Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2021, 12:09 PM
  • 29 0744_29 0743_02012021_043035.mp4

Date
02/01/2021
W/O
870407
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00527
PipeID
P24250
Time
4:09 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8385
Sewer Name
29 ALAMITOS PUMPING PLANT TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_870407_TV29078_JAN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0744
Downstream MH
29 0743
Dir. of Survey
Downstream
Length Surveyed
321.6 ft.
Total Length
321.6 ft.
Structural Index
3
Structural Quick
4K3L
Structural Rating
429
O&M Index
1
O&M Quick
4132
O&M Rating
60
Overall Index
3
Overall Quick
Overall Rating
489
Pipe schematic from manhole 29 0744 to 29 0743
MH: 29 0744MH: 29 0743downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 07440 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.5 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES19.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES19.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"51.5 ft. RML - Roots Medium Lateral, from 03 to 09 o'clock, 20 %, within 8 inches of joint: YES54.1 ft. RBL - Roots Ball Lateral, from 03 to 09 o'clock, 65 %54.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"110.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"181.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"266.8 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR266.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"313.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"318.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK321.6 ft. AMH - Downstream Manhole, Survey Ends - 29 0743

Observation photos (9)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    12.5 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    19.9 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.9 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 03 to 09 o'clock, 20 %, within 8 inches of joint: YES

    51.5 ft. - Roots Medium Lateral, from 03 to 09 o'clock, 20 %, within 8 inches of joint: YES

  • Roots Ball Lateral, from 03 to 09 o'clock, 65 %

    54.1 ft. - Roots Ball Lateral, from 03 to 09 o'clock, 65 %

  • Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR

    266.8 ft. - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    313.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

Observations (22)

DistanceCodeObservation
318.9SAP
0AMH29 0744
54.1RBL
313.5TB
24.9RFJ
0MWM
110.1TF
12.5RFJ
321.6AMH29 0743
318.8FM
181.3TF
51.5TF
311.1TFC
266.8RMJ
51.5RML
2SAP
54.1TF
0MWL
266.8RFJ
19.9RFJ
321.4MGOCONNECTION AT THE MH 3 OC'LOCK
19.9FM

Properties (6)

custom_field_three
AGGREGATE PROJECTING, FRACTURES
custom_field_two
2
customer
1
datetime
2021-02-01T04:09:01-08:00
documentation
PRO PIPE
is_lateral_inspection
false