Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2021, 09:49 AM
  • 03 0584_03 0400_01252021_023537.mp4

Date
01/25/2021
W/O
870242
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00371
PipeID
P04976
Time
1:49 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8505
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_870242_TV03173_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
27 in.
Upstream MH
03 0400
Downstream MH
03 0584
Dir. of Survey
Upstream
Length Surveyed
247.6 ft.
Total Length
247.6 ft.
Structural Index
4
Structural Quick
4300
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole 03 0400 to 03 0584
MH: 03 0400MH: 03 0584upstream0 ft. AMH - Upstream Manhole, Survey Ends - 03 058415.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25.9 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES31.1 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES247.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK247.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK247.6 ft. MWL - Water Level, 5 %of cross sectional area247.6 ft. MWM - Water Mark, 25 %of cross sectional area247.6 ft. AMH - Downstream Manhole, Survey Begins - 03 0400

Observation photos (3)

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    216.5 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    221.7 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    232.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
216.5FM
0MGOCONNECTION AT MH 3 O'CLOCK
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0MWM
0AMH03 0400
232.2FM
221.7FM
247.6AMH03 0584

Properties (7)

additional_info
630138012521001
custom_field_three
MULTIPLE FRACTURE
custom_field_two
2
customer
1
datetime
2021-01-25T01:49:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false