Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2021, 10:38 AM
  • 03 0400_03 0399_01252021_030439.mp4

Date
01/25/2021
W/O
870242
Weather
Heavy Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00371
PipeID
P04975
Time
2:38 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8505
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_870242_TV03173_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
03 0400
Downstream MH
03 0399
Dir. of Survey
Downstream
Length Surveyed
301.7 ft.
Total Length
301.7 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 03 0400 to 03 0399
MH: 03 0400MH: 03 0399downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 04000 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK17 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES43.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"96 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start103 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"151.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"202.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"292.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.7 ft. AMH - Downstream Manhole, Survey Ends - 03 0399

Observation photos (2)

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    17 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    96 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
301.7AMH03 0399
292.4FM
202.3TBA
198.1TFC
0MWM
0AMH03 0400
17FM
96FM
43.9TF
151.7TFC
0MGOCONNECTION AT MH 9 O'CLOCK
103TFC
0MGOCONNECTION AT MH 3 O'CLOCK
252.1TBA

Properties (7)

additional_info
630138012521001
custom_field_three
MULTIPLE FRACTURE
custom_field_two
2
customer
1
datetime
2021-01-25T02:38:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false