Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2021, 10:42 AM
  • 18 0488_18 1194_01262021_024859.mp4

Date
01/26/2021
W/O
870405
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00687
PipeID
P15040
Time
2:42 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8434
Sewer Name
18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_870405_TV18109_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1194
Downstream MH
18 0488
Dir. of Survey
Upstream
Length Surveyed
94.5 ft.
Total Length
94.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole 18 1194 to 18 0488
MH: 18 1194MH: 18 0488upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 18 04880.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish42.2 ft. CS - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES90.5 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES92.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start94.5 ft. AMH - Downstream Manhole, Survey Begins - 18 119494.5 ft. MWM - Water Mark, 15 %of cross sectional area94.5 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    52.3 ft. - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    94.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (9)

DistanceCodeObservation
52.3CS
2DAGS
0AMH18 1194
94.5MGOCOCKROACHES IN MANHOLE
94.5AMH18 0488
93.6DAGS
0MWM
0MWL
4CM

Properties (8)

additional_info
630069012521203
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-01-26T02:42:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31671