- Date
- 01/26/2021
- W/O
- 870405
- Weather
- Snow
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00687
- PipeID
- P15039
- Time
- 2:50 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8434
- Sewer Name
- 18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
- City
- WHITTIER
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_870405_TV18109_JAN2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 18 1194
- Downstream MH
- 18 1193
- Dir. of Survey
- Downstream
- Length Surveyed
- 243.9 ft.
- Total Length
- 243.9 ft.
- Structural Index
- 3
- Structural Quick
- 3H00
- Structural Rating
- 141
- O&M Index
- 2
- O&M Quick
- 2I00
- O&M Rating
- 96
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 237
Pipe schematic from manhole 18 1194 to 18 1193 Observation photos (4)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

9.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

243.9 ft. - General Observation - COCKROACHES IN MANHOLE