Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 4, 2021, 09:15 AM
  • B 0609_B 0608_342021_014952.mp4

Date
03/04/2021
W/O
0875029
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00105
PipeID
P09181
Time
1:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1739
Sewer Name
B JOINT OUTFALL B - UNIT 8B
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
20210304MDM_JOINT_OUTFALL_B_UNIT_8B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
B 0609
Downstream MH
B 0608
Dir. of Survey
Downstream
Length Surveyed
353.7 ft.
Total Length
353.7 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole B 0609 to B 0608
MH: B 0609MH: B 0608downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM2 ft. MGO - General Observation - MAG COAT 98% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT29.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT107 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT294.2 ft. MGO - General Observation - 98% MAG COAT353.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISDTERING PEELING CONCRET UNDER MAG COAT353.2 ft. MGO - General Observation - 98% MAG COAT FINISH353.7 ft. AMH - Downstream Manhole, Survey Ends - 2:25AM

Observation photos (5)

  • General Observation - MAG COAT 98% START

    2 ft. - General Observation - MAG COAT 98% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

    29.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

    107 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

  • General Observation - 98% MAG COAT

    294.2 ft. - General Observation - 98% MAG COAT

Observations (11)

DistanceCodeObservation
353.7AMH2:25AM
0MWL
353.2SSSBLISDTERING PEELING CONCRET UNDER MAG COAT
2MGOMAG COAT 98% START
294.2MGO98% MAG COAT
29.6SSSPEELING CONCRETE UNDER MAG COAT
107SSSPEELING CONCRETE UNDER MAG COAT
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWM
0AMH1:55AM
353.2MGO98% MAG COAT FINISH

Properties (6)

custom_field_three
MAG COAT 98%
custom_field_two
4
customer
LACSD
datetime
2021-03-04T01:15:09-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false