Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2021, 06:35 PM
  • 05 0140_05 0139_01112021_111910.mp4

Date
01/11/2021
W/O
865118
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00431
PipeID
P05432
Time
10:35 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8096
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHORNE
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_865118_TV05373_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
27 in.
Upstream MH
05 0140
Downstream MH
05 0139
Dir. of Survey
Downstream
Length Surveyed
313.4 ft.
Total Length
313.4 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole 05 0140 to 05 0139
MH: 05 0140MH: 05 0139downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01402 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start8 ft. MGO - General Observation - MAG COAT START310.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish311.3 ft. MGO - General Observation - MAG COATING END313.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0139

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
311.3MGOMAG COATING END
313.4AMH05 0139
8MGOMAG COAT START
0MWL
310.8SAV
0AMH05 0140
2SAV

Properties (7)

additional_info
630098011121053
custom_field_three
AGGREGATE VISIBLE
custom_field_two
4
customer
1
datetime
2021-01-11T10:35:13-08:00
documentation
PROPIPE
is_lateral_inspection
false