Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 21, 2021, 01:54 PM
  • 05 0137_05 0136_01212021_062822.mp4

Date
01/21/2021
W/O
865118
Weather
Dry
Operator/Surveyor
E. RUIZ
Sewer ID
Z00431
PipeID
P05428
Time
5:54 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7780
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHORNE
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_865118_TV05373_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
42 in.
Upstream MH
05 0137
Downstream MH
05 0136
Dir. of Survey
Downstream
Length Surveyed
319.6 ft.
Total Length
319.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
315
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 05 0137 to 05 0136
MH: 05 0137MH: 05 0136downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 01370 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. MGO - General Observation - SURFACE REINFORCEMENT VISIBLE @ 12 O'CLOCK2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start319.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK319.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish319.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish319.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0136319.6 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (5)

  • General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

    0 ft. - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

    319.4 ft. - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

  • General Observation - COCKROACHES IN MH

    319.6 ft. - General Observation - COCKROACHES IN MH

Observations (10)

DistanceCodeObservation
0AMH05 0137
2MGOSURFACE REINFORCEMENT VISIBLE @ 12 O'CLOCK
4.1SSS
319.6AMH05 0136
319.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
319.4SAP
2.1SAP
319.4SSS
319.6MGOCOCKROACHES IN MH

Properties (6)

custom_field_three
SURFACE AGG.,SURFACE SPALNG.,SRFC. REINFRC. VISBL.
custom_field_two
2
customer
1
datetime
2021-01-21T05:54:51-08:00
documentation
PROPIPE
is_lateral_inspection
false