Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 11:17 AM
  • 05 0098_05 0097_12302020_035125.mp4

Date
12/30/2020
W/O
865118
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05388
Time
3:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8342
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_865118_TV05373_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
05 0098
Downstream MH
05 0097
Dir. of Survey
Downstream
Length Surveyed
330.9 ft.
Total Length
330.9 ft.
Structural Index
3
Structural Quick
5K3L
Structural Rating
630
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
630
Pipe schematic from manhole 05 0098 to 05 0097
MH: 05 0098MH: 05 0097downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 00980 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH, 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start330.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.9 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK330.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish330.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0097

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    27.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWM
330.9SAP
27.5SRV
4SSS
330.9SSS
4SAP
0AMH05 0098
0MGOCONNECTION AT MH, 3 O'CLOCK
330.9MGOCONNECTION AT MH, 9 O'CLOCK
330.9SRV
0MGOACTIVE CONNECTION AT MH, 9 O'CLOCK
0MWL
330.9AMH05 0097

Properties (7)

additional_info
630138122920202
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2020-12-30T03:17:05-08:00
documentation
PROPIPE
is_lateral_inspection
false