Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2021, 10:51 AM
  • 05 0097_05 0096_01142021_033643.mp4

Date
01/14/2021
W/O
865118
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05387
Time
2:51 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8459
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_865118_TV05373_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
05 0097
Downstream MH
05 0096
Dir. of Survey
Downstream
Length Surveyed
325.2 ft.
Total Length
325.2 ft.
Structural Index
3
Structural Quick
5I3L
Structural Rating
570
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
570
Pipe schematic from manhole 05 0097 to 05 0096
MH: 05 0097MH: 05 0096downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 00976.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start75.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start325.2 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK325.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish325.2 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK325.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0096

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    75.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
6.8SAP
0MWM
325.2MGOCONNECTION AT MH, 9 O'CLOCK
325.2SSS
325.2SAP
6.8SSS
325.2SRV
0MWL
325.2MGOCONNECTION AT MH, 3 O'CLOCK
75.8SRV
0AMH05 0097
325.2AMH05 0096

Properties (7)

additional_info
630075011321202
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/SPALLIN
custom_field_two
2
customer
1
datetime
2021-01-14T02:51:12-08:00
documentation
PROPIPE
is_lateral_inspection
false