Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2021, 09:19 AM
  • 05 2575_05 2574_01132021_013029.mp4

Date
01/13/2021
W/O
865008
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01131
PipeID
P25277
Time
1:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8457
Sewer Name
05 COLDEN AVENUE RELIEF TRUNK
City
S.LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_865008_TV05127_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2575
Downstream MH
05 2574
Dir. of Survey
Downstream
Length Surveyed
302.8 ft.
Total Length
302.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 05 2575 to 05 2574
MH: 05 2575MH: 05 2574downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 25750 ft. MWM - Water Mark, 20 %of cross sectional area194.4 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES302.8 ft. AMH - Downstream Manhole, Survey Ends - 05 2574

Observation photos (1)

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    194.4 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
194.4CS
0MWL
0AMH05 2575
302.8AMH05 2574
0MWM

Properties (8)

additional_info
630075011221201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-13T01:19:00-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38590