Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2021, 11:03 AM
  • 29 0268A_29 0268_01282021_032030.mp4

Date
01/28/2021
W/O
870549
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24174
Time
3:03 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8460
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_870549_TV29063_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0268
Downstream MH
29 0268A
Dir. of Survey
Upstream
Length Surveyed
222.3 ft.
Total Length
222.3 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
133
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
133
Pipe schematic from manhole 29 0268 to 29 0268A
MH: 29 0268MH: 29 0268Aupstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. ACOM - Cleanout Mainline, Survey Ends - 29 0268A3.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"10.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"43.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start219.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES222.3 ft. MWM - Water Mark, 5 %of cross sectional area222.3 ft. AMH - Downstream Manhole, Survey Begins - 29 0268222.3 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    156.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (17)

DistanceCodeObservation
211.8TF
219.2TFC
179.1TF
3.2FM
222.3CM
170.8TFC
0MWM
222.3ACOM29 0268A
156.2TB
6CM
138.1TFC
79TFC
76.7TFC
67.9TF
0AMH29 0268
120.4TFC
0MWL

Properties (7)

additional_info
SC411973
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-01-28T03:03:52-08:00
documentation
PROPIPE
is_lateral_inspection
false