Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2021, 11:54 AM
  • 29 0267_29 0266_01282021_042111.mp4

Date
01/28/2021
W/O
870549
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24172
Time
3:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8460
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_870549_TV29063_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0267
Downstream MH
29 0266
Dir. of Survey
Downstream
Length Surveyed
331 ft.
Total Length
331 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
208
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
208
Pipe schematic from manhole 29 0267 to 29 0266
MH: 29 0267MH: 29 0266downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02674.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"58.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.6 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES213.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"218.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"259.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES323.9 ft. H - Hole, from 10 to 12 o'clock, within 8 inches of joint: YES331 ft. AMH - Downstream Manhole, Survey Ends - 29 0266331 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    212.6 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    213.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    323.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Hole, from 10 to 12 o'clock, within 8 inches of joint: YES

    323.9 ft. - Hole, from 10 to 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
331AMH29 0266
0MWM
213.6TB
11.1TF
102.9TF
331CM
212.6FM
165.2TF
8.4TFC
5.6TF
4.4CM
323.3FM
215.9TF
64.3TF
323.9H
0MWL
218.5TFC
309.6TF
256.5TF
58.7TF
259.3TF
120.5TF
0AMH29 0267

Properties (7)

additional_info
SC411973
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-01-28T03:54:54-08:00
documentation
PROPIPE
is_lateral_inspection
false