Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2021, 09:32 AM
  • 29 0262_29 0261_01282021_015208.mp4

Date
01/28/2021
W/O
870549
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24166
Time
1:32 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8460
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_870549_TV29063_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0261
Downstream MH
29 0262
Dir. of Survey
Upstream
Length Surveyed
322.8 ft.
Total Length
322.8 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
193
Pipe schematic from manhole 29 0261 to 29 0262
MH: 29 0261MH: 29 0262upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 02620 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish4.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.9 ft. RBL - Roots Ball Lateral, at 10 o'clock, 70 %111.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"315.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start322.8 ft. MWL - Water Level, 5 %of cross sectional area322.8 ft. AMH - Downstream Manhole, Survey Begins - 29 0261322.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK322.8 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Ball Lateral, at 10 o'clock, 70 %

    210.9 ft. - Roots Ball Lateral, at 10 o'clock, 70 %

Observations (14)

DistanceCodeObservation
322.8AMH29 0262
7.3CM
0MWL
318.3TF
0AMH29 0261
270.4TFC
33.9TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
210.9RBL
151.3TF
0MWM
91.7TF
210.9TF
322.8CM

Properties (7)

additional_info
SC411973
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-01-28T01:32:30-08:00
documentation
PROPIPE
is_lateral_inspection
false