Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2021, 07:58 AM
  • J 0051_J 0050_02102021_000535.mp4

Date
02/09/2021
W/O
870730
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00062
PipeID
P11628
Time
11:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8471
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_870730_TV05287_JAN2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
J 0051
Downstream MH
J 0050
Dir. of Survey
Downstream
Length Surveyed
233.8 ft.
Total Length
233.8 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
230
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
230
Pipe schematic from manhole J 0051 to J 0050
MH: J 0051MH: J 0050downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00512.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COAT2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start233.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish233.8 ft. AMH - Downstream Manhole, Survey Ends - J 0050233.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2.6SAP
0MWM
0MWL
233.8SAP
233.8AMHJ 0050
233.8SSS
2.6MGOMAG COAT
0AMHJ 0051
2.6SSS

Properties (7)

additional_info
630074020921202
custom_field_three
SPALLING/ AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-02-09T23:58:25-08:00
documentation
PROPIPE
is_lateral_inspection
false