Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2021, 06:57 AM
  • 22 0248_22 0247_02082021_231542.mp4

Date
02/08/2021
W/O
870521
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00793
PipeID
P16530
Time
10:57 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8396
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_870521_TV22160_JAN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0248
Downstream MH
22 0247
Dir. of Survey
Downstream
Length Surveyed
290.8 ft.
Total Length
290.8 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
285
O&M Index
3
O&M Quick
3311
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
295
Pipe schematic from manhole 22 0248 to 22 0247
MH: 22 0248MH: 22 0247downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02482.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. MGO - General Observation - MAG COAT2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"51.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"81.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"102.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"126.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"133.7 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR156.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"161.1 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES173.4 ft. RMJ - Roots Medium Joint, from 11 to 02 o'clock, 15 %, within 8 inches of joint: YESR180.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"202.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"220.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"233.6 ft. RMJ - Roots Medium Joint, from 11 to 01 o'clock, 5 %, within 8 inches of joint: YESR247 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"289.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0247290.8 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.4 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    133.7 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

    161.1 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 11 to 02 o'clock, 15 %, within 8 inches of joint: YESR

    173.4 ft. - Roots Medium Joint, from 11 to 02 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 11 to 01 o'clock, 5 %, within 8 inches of joint: YESR

    233.6 ft. - Roots Medium Joint, from 11 to 01 o'clock, 5 %, within 8 inches of joint: YESR

Observations (24)

DistanceCodeObservation
2.4SAP
233.6RMJ
290.8AMH22 0247
161.1RFJ
2.4MGOMAG COAT
51.4TFC
0MWL
220.1TFC
30.3TFC
180.8TFC
2.4SSS
202.2TFC
0MWM
156.7TFC
290.8MGOCONNECTION AT MH, 3 O'CLOCK
126.7TFC
247TFC
81.3TFC
0AMH22 0248
133.7RMJ
102.5TFC
289.1SSS
173.4RMJ
289.1SAP

Properties (6)

custom_field_three
AGGREGATE PROJECTING,SPALLING
custom_field_two
3
customer
1
datetime
2021-02-08T22:57:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false