Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2021, 07:29 AM
  • 22 0283_22 0282_02022021_235008.mp4

Date
02/02/2021
W/O
870414
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00793
PipeID
P16569
Time
11:29 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8389
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_870414_TV22014_JAN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0283
Downstream MH
22 0282
Dir. of Survey
Downstream
Length Surveyed
293.8 ft.
Total Length
293.8 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
290
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 22 0283 to 22 0282
MH: 22 0283MH: 22 0282downstream0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 02830 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"27 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"29.7 ft. MGO - General Observation - MAG COAT91.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"136.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"147.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"152.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"208.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"253.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"281.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"291.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.8 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK293.8 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK293.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0282

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    29.7 ft. - General Observation - MAG COAT

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    136.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

Observations (21)

DistanceCodeObservation
293.8MGOCONNECTION AT MH, 3 O'CLOCK
147.9TFC
2.5SAP
136.2TB
291.9SSS
0MGOCONNECTION AT MH, 3 O'CLOCK
0AMH22 0283
0MWM
91.5TFA
152.5TFA
281.5TF
291.9SAP
0MWL
253.3TF
208.8TF
293.8MGOCONNECTION AT MH, 9 O'CLOCK
2.5SSS
27TF
6.8TF
293.8AMH22 0282
29.7MGOMAG COAT

Properties (6)

custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2021-02-02T23:29:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false