Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2021, 11:14 AM
  • 05 0279_05 0278_2222021_031826.mp4

Date
02/22/2021
W/O
0875039
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00498
PipeID
P05486
Time
3:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1727
Sewer Name
05 OAK STREET-CENTER AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20210217MDM_OAK_STREET_CENTER_AVENUE_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
05 0279
Downstream MH
05 0278
Dir. of Survey
Downstream
Length Surveyed
324.7 ft.
Total Length
324.7 ft.
Structural Index
3
Structural Quick
4221
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 05 0279 to 05 0278
MH: 05 0279MH: 05 0278downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG217.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG324.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish324.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED324.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG324.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active324.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active324.7 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    217.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (14)

DistanceCodeObservation
0MGOConn. @ Mh, 9 O' Clock. Active
324.2DAGS
0MWL
2DAGS
2SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
324.2SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
0MWM
2SAMSEVERE AGG
324.2SAMSEVERE AGG
324.7AMH3:40AM
324.2MGOConn. @ Mh, 3 O' Clock. Active
0AMH3:20AM
324.2MGOConn. @ Mh, 9 O' Clock. Active
217.7SAMSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2021-02-22T03:14:21-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false