Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 09:28 AM
  • 05 0301_05 0300_2182021_013146.mp4

Date
02/18/2021
W/O
0875039
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00498
PipeID
P05509
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1724
Sewer Name
05 OAK STREET-CENTER AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20210217MDM_OAK_STREET_CENTER_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
22 in.
Upstream MH
05 0301
Downstream MH
05 0300
Dir. of Survey
Downstream
Length Surveyed
329.9 ft.
Total Length
329.9 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
14
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 0301 to 05 0300
MH: 05 0301MH: 05 0300downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE40.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE93 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG212.6 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCK329.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE329.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active329.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC329.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG329.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active329.9 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observation photos (5)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    40.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    93 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Deposits Settled Other,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - ROCK

    212.6 ft. - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCK

Observations (16)

DistanceCodeObservation
329.3SSSBLISTERING PEELING CONCRETE
40.4SSSBLISTERING PEELING CONCRETE
0MWM
93SAVSEVERE AGG
329.3MGOConn. @ Mh, 9 O' Clock. Active
329.3SAMSEVERE AGG SPORATIC
329.3SAVSEVERE AGG
2SAMSEVERE AGG
0MWL
2SAVSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. OPEN
2SSSBLISTERING PEELING CONCRETE
212.6DSZROCK
329.3MGOConn. @ Mh, 3 O' Clock. Active
329.9AMH2:00AM
0AMH1:30AM

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2021-02-18T01:28:56-08:00
documentation
MARTIN,CASTILLO,RUVALCABA
is_lateral_inspection
false