Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2021, 07:07 AM
  • 05 1998_05 1997_01282021_233945.mp4

Date
01/28/2021
W/O
870570
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00538
PipeID
P07190
Time
11:07 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8512
Sewer Name
05 WESTERN AVENUE TRUNK
City
RANCHO PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
44
Purpose
Routine Assessment
Project
WO_870570_TV05115_JAN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
05 1998
Downstream MH
05 1997
Dir. of Survey
Downstream
Length Surveyed
246.2 ft.
Total Length
246.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
96
Pipe schematic from manhole 05 1998 to 05 1997
MH: 05 1998MH: 05 1997downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 19980 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start57.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN244 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish246.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1997

Observations (8)

DistanceCodeObservation
0AMH05 1998
246.2AMH05 1997
57.3TFOPEN
2DAGS
0MWL
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
244DAGS

Properties (8)

additional_info
630138012821201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-01-28T23:07:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP