Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2021, 09:34 AM
  • 05 1997_05 1996_01292021_015406.mp4

Date
01/29/2021
W/O
870570
Weather
Heavy Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00538
PipeID
P07189
Time
1:34 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8512
Sewer Name
05 WESTERN AVENUE TRUNK
City
RANCHO PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
44
Purpose
Routine Assessment
Project
WO_870570_TV05115_JAN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
05 1996
Downstream MH
05 1997
Dir. of Survey
Upstream
Length Surveyed
122.3 ft.
Total Length
122.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
50
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 05 1996 to 05 1997
MH: 05 1996MH: 05 1997upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 19970.3 ft. MGO - General Observation - ROACHES @ MH2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish111.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4" - 25% GREASE-LATERAL/OPEN120.3 ft. MGO - General Observation - PIPE IS LINED120.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start122.3 ft. AMH - Downstream Manhole, Survey Begins - 05 1996122.3 ft. MWL - Water Level, 20 %of cross sectional area122.3 ft. MWM - Water Mark, 25 %of cross sectional area

Observations (9)

DistanceCodeObservation
0AMH05 1996
0MWL
10.5TFD25% GREASE-LATERAL/OPEN
122MGOROACHES @ MH
120DAGS
122.3AMH05 1997
2MGOPIPE IS LINED
0MWM
2DAGS

Properties (8)

additional_info
630138012821201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-01-29T01:34:45-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP