Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2021, 09:53 AM
  • 08 0038_08 0037_02032021_020448.mp4

Date
02/03/2021
W/O
870237
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00016
PipeID
P00040
Time
1:53 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7833
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_870237_TV08115_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
24 in.
Upstream MH
08 0038
Downstream MH
08 0037
Dir. of Survey
Downstream
Length Surveyed
167.4 ft.
Total Length
167.4 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
68
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
134
Pipe schematic from manhole 08 0038 to 08 0037
MH: 08 0038MH: 08 0037downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00380 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"10.7 ft. MGO - General Observation - STEAM IN SEWER55.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"106.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4" - OPEN154.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"162.3 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES165 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish165 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167 ft. MGO - General Observation - ROACHES @ MH167.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE167.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0037

Observation photos (2)

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"

    55.6 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    162.3 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
165DAGS
162.3CS
0MWM
2SSS
7TFC
55.6TFC
106.7TFOPEN
167.4MGOCONN @ MH 9 O'CLOCK/ACTIVE
154.3TFC
167.4AMH08 0037
167MGOROACHES @ MH
2DAGS
0AMH08 0038
165SSS
10.7MGOSTEAM IN SEWER
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
0MWL

Properties (7)

additional_info
630138020221201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-02-03T01:53:18-08:00
documentation
PROPIPE
is_lateral_inspection
false