Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2021, 12:29 PM
  • 03 0388_03 MARINA_01252021_043950.mp4

Date
01/25/2021
W/O
870235
Weather
Light Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00371
PipeID
P05285
Time
4:29 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8506
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_870235_TV03135_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
36 in.
Upstream MH
03 0388
Downstream MH
03 MARINA
Dir. of Survey
Downstream
Length Surveyed
4.9 ft.
Total Length
5 ft.
Structural Index
2
Structural Quick
3121
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 03 0388 to 03 MARINA
MH: 03 0388MH: 03 MARINAdownstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 03880 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES3 ft. CM - Crack Multiple, from 03 to 10 o'clock, within 8 inches of joint: YES3 ft. JOM - Joint Offset Medium4.9 ft. AMH - Downstream Manhole, Survey Ends - 03 MARINA

Observation photos (2)

  • Crack Multiple, from 03 to 10 o'clock, within 8 inches of joint: YES

    3 ft. - Crack Multiple, from 03 to 10 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    3 ft. - Joint Offset Medium

Observations (9)

DistanceCodeObservation
2SSS
0MWM
0AMH03 0388
0MWL
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
4.9AMH03 MARINA
3CM
3JOM

Properties (6)

custom_field_three
FRACTURE/OFFSET
custom_field_two
3
customer
1
datetime
2021-01-25T04:29:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false