Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2015, 10:20 AM
Date
09/02/2015
W/O
0521101
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00226
PipeID
P02108
Time
3:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6502
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20150902MDM_WILC0X_AVENUE_TRUNK_EXTENSION_1
Material
CIP
Shape
Circular
Height
16 in.
Upstream MH
01 1198
Downstream MH
01 1155
Dir. of Survey
Downstream
Length Surveyed
87.8 ft.
Total Length
87.8 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 01 1198 to 01 1155
MH: 01 1198MH: 01 1155downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MMC - Material Change, Vitrified clay pipe11.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES17.3 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT20.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT26.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT26.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT32.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT36.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT37.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB38.6 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE41.7 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE44.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE48.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE50.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE54.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT56.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT65.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT69.1 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES71.1 ft. MMC - Material Change, Cast Iron71.1 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 20% CORRISON81.3 ft. MGP - General Photograph - CIP 20% CORRISON83.9 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, - 30%84.8 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish84.8 ft. MGP - General Photograph - 30% CORRISON86.9 ft. SMW - Surface Missing Wall, from 08 to 04 o'clock, within 8 inches of joint: YES - APPOX 1.5" WIDE86.9 ft. MGP - General Photograph87.8 ft. AMH - Downstream Manhole, Survey Ends - 4:20AM

Observation photos (9)

  • Material Change, Vitrified clay pipe

    2 ft. - Material Change, Vitrified clay pipe

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    56.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Material Change, Cast Iron

    71.1 ft. - Material Change, Cast Iron

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 20% CORRISON

    71.1 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 20% CORRISON

  • General Photograph - CIP 20% CORRISON

    81.3 ft. - General Photograph - CIP 20% CORRISON

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES,  - 30%

    83.9 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, - 30%

  • General Photograph - 30% CORRISON

    84.8 ft. - General Photograph - 30% CORRISON

  • Surface Missing Wall, from 08 to 04 o'clock, within 8 inches of joint: YES - APPOX 1.5" WIDE

    86.9 ft. - Surface Missing Wall, from 08 to 04 o'clock, within 8 inches of joint: YES - APPOX 1.5" WIDE

  • General Photograph

    86.9 ft. - General Photograph

Observations (30)

DistanceCodeObservation
87.8AMH4:20AM
56.9FMSLIGHT
71.1MMC
81.3MGPCIP 20% CORRISON
37.6TFCSTUB
84.8SCP
2MMC
86.9SMWAPPOX 1.5" WIDE
48.2FCHAIRLINE
86.9MGP
38.6FCHAIRLINE
65.6FCSLIGHT
17.3FCSLIGHT
26.9FCSLIGHT
54.1FCSLIGHT
11.5CL
0AMH3:45AM
83.9SCP30%
84.8MGP30% CORRISON
36.1FCSLIGHT
26.9FCSLIGHT
20.5FCSLIGHT
41.7FCHAIRLINE
69.1CC
0MWL
44.7FCHAIRLINE
32.6FCSLIGHT
50.8FCHAIRLINE
0MWM
71.1SCP20% CORRISON

Properties (6)

custom_field_three
MISSING WALL SOIL VISIBLE-8 TO 4-- 1.5" WIDE
custom_field_two
1
customer
LACSD
datetime
2015-09-02T03:20:44-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false