Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2021, 09:58 AM
  • H 0929_H 0928_01132021_022801.mp4

Date
01/13/2021
W/O
865007
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01005
PipeID
P15342
Time
1:58 AM
Certificate
U-115-06002794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8376
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_865007_TV21022_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0929
Downstream MH
H 0928
Dir. of Survey
Downstream
Length Surveyed
447.4 ft.
Total Length
447.4 ft.
Structural Index
3
Structural Quick
3b2b
Structural Rating
865
O&M Index
2
O&M Quick
2Q00
O&M Rating
178
Overall Index
2
Overall Quick
Overall Rating
1043
Pipe schematic from manhole H 0929 to H 0928
MH: H 0929MH: H 0928downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - H 09292 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 65% MAG COAT20.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start398.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 12" - OPEN442.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish442.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish445 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish445 ft. MGO - General Observation - ROACHES @ MH445 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish445 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish447.4 ft. AMH - Downstream Manhole, Survey Ends - H 0928

Observation photos (4)

  • General Observation - 65% MAG COAT

    2 ft. - General Observation - 65% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 12" - OPEN

    398.6 ft. - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 12" - OPEN

Observations (19)

DistanceCodeObservation
20.5SSS
2SSS
445SSS
442.7SAP
442.7SSS
0MWL
447.4AMHH 0928
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2SAV
0MWM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
445MGOROACHES @ MH
2DAGS
20.5SAP
398.6TFOPEN
0AMHH 0929
2MGO65% MAG COAT
445DAGS
445SAV

Properties (6)

custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-01-13T01:58:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false