Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2021, 05:33 PM
  • H 0963_H 0962_01122021_095341.mp4

Date
01/12/2021
W/O
865007
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z01005
PipeID
P15376
Time
9:33 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8097
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Routine Assessment
Project
WO_865007_TV21022_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0963
Downstream MH
H 0962
Dir. of Survey
Downstream
Length Surveyed
437.5 ft.
Total Length
437.5 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
435
O&M Index
2
O&M Quick
2P00
O&M Rating
174
Overall Index
2
Overall Quick
Overall Rating
609
Pipe schematic from manhole H 0963 to H 0962
MH: H 0963MH: H 0962downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 09630 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - 65% MAG COAT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start149.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"166.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN387.5 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6"435 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish435 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish435 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish437.5 ft. AMH - Downstream Manhole, Survey Ends - H 0962

Observations (15)

DistanceCodeObservation
435DAGS
0MWM
2MGO65% MAG COAT
149.1TFA
0AMHH 0963
387.5TBA
437.5AMHH 0962
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
166.5TFOPEN
0MWL
435SSS
435SAV
2SAV
2DAGS
2SSS

Properties (6)

custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-01-12T09:33:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false