Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 19, 2021, 09:48 AM
  • 22 0302_22 0301_01192021_020410.mp4

Date
01/19/2021
W/O
870228
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00794
PipeID
P16589
Time
1:48 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8382
Sewer Name
22 CAMERON TRUNK, SECTION 4
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_870228_TV22013_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0302
Downstream MH
22 0301
Dir. of Survey
Downstream
Length Surveyed
294.8 ft.
Total Length
294.8 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 22 0302 to 22 0301
MH: 22 0302MH: 22 0301downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 03020 ft. MGO - General Observation - CONNECTION AT MH 3 & 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area7.2 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES9.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES22.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"88.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"95 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"144.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"202.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"208.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"263 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"287.3 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - .292.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK294.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0301

Observation photos (4)

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    7.2 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    22.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - .

    287.3 ft. - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES - .

Observations (18)

DistanceCodeObservation
88.4TFC
9.9CM
0MWL
263TFC
30.6TFC
294.8MGOCONNECTION AT MH 9 O'CLOCK
292.4CM
0AMH22 0302
22.3CM
0MGOCONNECTION AT MH 3 & 9 O'CLOCK
144.7TFC
294.8AMH22 0301
95TF
208.8TF
202.6TFC
7.2FM
0MWM
287.3RPP.

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-01-19T01:48:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false