Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2021, 09:49 AM
  • 02 0574_02 0573_01222021_020210.mp4

Date
01/22/2021
W/O
864827
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00244
PipeID
P02893
Time
1:49 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8429
Sewer Name
02 DISTRICT #2 MAIN TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_864827_TV02091_DEC2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
33 in.
Width
42 in.
Upstream MH
02 0574
Downstream MH
02 0573
Dir. of Survey
Downstream
Length Surveyed
323.7 ft.
Total Length
323.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
413L
O&M Rating
321
Overall Index
3
Overall Quick
Overall Rating
321
Pipe schematic from manhole 02 0574 to 02 0573
MH: 02 0574MH: 02 0573downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 05740 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.6 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS321.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish321.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE323.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0573323.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    323.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
323.7MGOCOCKROACHES IN MANHOLE
2MGOMAG COATING THROUGHOUT
0AMH02 0574
0MWM
321.3DAGS
323.7AMH02 0573
323.7MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
8.6DSZDEBRIS
321.3DSZ
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630069012121204
custom_field_three
MAG COATING/DEBRIS
custom_field_two
5
customer
1
datetime
2021-01-22T01:49:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false