Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2021, 09:56 AM
  • 02 0567_02 0566_01252021_020820.mp4

Date
01/25/2021
W/O
864827
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00244
PipeID
P02886
Time
1:56 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8430
Sewer Name
02 DISTRICT #2 MAIN TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_864827_TV02091_DEC2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
33 in.
Width
42 in.
Upstream MH
02 0567
Downstream MH
02 0566
Dir. of Survey
Downstream
Length Surveyed
172.3 ft.
Total Length
172.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 02 0567 to 02 0566
MH: 02 0567MH: 02 0566downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 05670 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start146.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS171.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish172.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK172.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0566172.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2MGOMAG COATING THROUGHOUT
172.3AMH02 0566
0MWL
171.2DAGS
0AMH02 0567
146.2DSZDEBRIS
172.2MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
172.3MGOCONNECTION AT MH 9 O'CLOCK
0MWM

Properties (7)

additional_info
630069012521001
custom_field_three
MAG COATING
custom_field_two
5
customer
1
datetime
2021-01-25T01:56:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false