Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2021, 05:08 PM
  • 1_1_1_26012021_112656.mp4

Date
01/26/2021
W/O
0875106
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00334
PipeID
P08416
Time
9:08 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0370
Sewer Name
JOINT OUTFALL A - UNIT 3C
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20210126DF_JOINT_OUTFALL_A_UNIT_3C
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
78 in.
Width
78 in.
Upstream MH
A 0041
Downstream MH
A 0040
Dir. of Survey
Downstream
Length Surveyed
1095 ft.
Total Length
1095 ft.
Structural Index
4
Structural Quick
5h3j
Structural Rating
1666
O&M Index
2
O&M Quick
2k00
O&M Rating
442
Overall Index
3
Overall Quick
Overall Rating
2108
Pipe schematic from manhole A 0041 to A 0040
MH: A 0041MH: A 0040downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:15 AM0.1 ft. MWL - Water Level, 25 %of cross sectional area0.1 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. MGO - General Observation - 30% MAG COAT80 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES80 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, at 02 o'clock, , within 8 inches of joint: YES1095 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1095 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1095 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1095 ft. AMH - Downstream Manhole, Survey Ends - 12:16 PM

Observations (13)

DistanceCodeObservation
0.1MWL
9SAP
1095DAGS
2DAGS
0.1MWM
9MGO30% MAG COAT
180DAR
80DAR
1095SAP
0AMH9:15 AM
1095SRV
1095AMH12:16 PM
80SRV

Properties (6)

custom_field_three
REINFORCEMENT/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-01-26T09:08:50-08:00
documentation
FRANKLIN, IGNACIO, BRAR, RAMIREZ
is_lateral_inspection
false