Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2016, 08:43 AM
  • 08 0464_08 0463_8152016_042249.mp4

Date
08/15/2016
W/O
0585838
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00520
Time
1:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0238
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20160813MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0464
Downstream MH
08 0463
Dir. of Survey
Downstream
Length Surveyed
245.6 ft.
Total Length
245.6 ft.
Structural Index
5
Structural Quick
5A41
Structural Rating
59
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
63
Pipe schematic from manhole 08 0464 to 08 0463
MH: 08 0464MH: 08 0463downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. Active2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR2 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:00 START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CIRCUN & LONG21.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR65.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - 90% OR MORE MISSING REBAR88.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - 905OR MORE MISSING REBAR109.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR126.6 ft. MGP - General Photograph126.6 ft. SMW - Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES - 8" X8" SOIL VISIBLE126.6 ft. MGP - General Photograph - SOIL VISIBLE146.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES178.2 ft. SMW - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 15" X4" SOIL VISIBLE178.4 ft. SMW - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 2" X2" SOIL VISIBLE178.4 ft. SMW - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 1" X1" SOIL VISIBLE178.4 ft. MGP - General Photograph - SOIL VISIBLE230.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active245.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED BEYOUND REBAR245.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG245.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR245.6 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (16)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

  • General Observation - MISSING TILES 100% 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00 START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CIRCUN & LONG

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CIRCUN & LONG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    21.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - 90% OR MORE MISSING REBAR

    65.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - 90% OR MORE MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - 905OR MORE MISSING REBAR

    88.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - 905OR MORE MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    109.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

  • General Photograph

    126.6 ft. - General Photograph

  • Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES - 8" X8" SOIL VISIBLE

    126.6 ft. - Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES - 8" X8" SOIL VISIBLE

  • General Photograph - SOIL VISIBLE

    126.6 ft. - General Photograph - SOIL VISIBLE

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    146.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 15" X4" SOIL VISIBLE

    178.2 ft. - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 15" X4" SOIL VISIBLE

  • Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 2" X2" SOIL VISIBLE

    178.4 ft. - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 2" X2" SOIL VISIBLE

  • Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 1" X1" SOIL VISIBLE

    178.4 ft. - Surface Missing Wall, from 09 to 10 o'clock, within 8 inches of joint: NO - 1" X1" SOIL VISIBLE

  • General Photograph - SOIL VISIBLE

    178.4 ft. - General Photograph - SOIL VISIBLE

Observations (26)

DistanceCodeObservation
245.3SRCCORRODED BEYOUND REBAR
2SAMSEVERER AGG
2SRCCORRODED BEYOUND REBAR
65.3SRC90% OR MORE MISSING REBAR
0MWL
0MWM
178.4SMW2" X2" SOIL VISIBLE
126.6MGP
126.6SMW8" X8" SOIL VISIBLE
2MGOMISSING TILES 100% 9:00 TO 3:00 START
245.3SAMSEVERE AGG
21.2SRCCORRODED BEYOUND REBAR
245.6AMH5:10AM
0MGOConn. @ Mh, 9 O' Clock. Capped
109.9SRCCORRODED BEYOUND REBAR
178.2SMW15" X4" SOIL VISIBLE
88.9SRC905OR MORE MISSING REBAR
245.3SRCBROKEN MISSING REBAR
178.4SMW1" X1" SOIL VISIBLE
230.1TFActive
178.4MGPSOIL VISIBLE
0AMH4:20AM
146.5SRC
0MGOConn. @ Mh, 6 O' Clock. Active
126.6MGPSOIL VISIBLE
2SRCBROKEN MISSING REBAR CIRCUN & LONG

Properties (6)

custom_field_three
MISSING WALL SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2016-08-15T01:43:20-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false