Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2017, 11:35 PM
  • 17 0022_17 0021 _02082017_000400.mp4

Date
01/26/2017
W/O
618954
Weather
Light Rain
Operator/Surveyor
JUAN B
Sewer ID
Z00668
PipeID
P13746
Time
3:35 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4234
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Routine Assessment
Project
WO_618954_TV17003_FEB2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
17 0022
Downstream MH
17 0021
Dir. of Survey
Downstream
Length Surveyed
344 ft.
Total Length
344 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
136
Pipe schematic from manhole 17 0022 to 17 0021
MH: 17 0022MH: 17 0021downstream0 ft. AMH - Upstream Manhole, Survey Begins - 17 00220 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.5 ft. MGO - General Observation - CIPP LINING29.3 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"37.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"85.2 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"121.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"162.1 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"169.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"193 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 4"232.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"269.2 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"288.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"344 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish344 ft. AMH - Downstream Manhole, Survey Ends - 17 0021

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0AMH17 0022
344DAGS
2.8DAGS
29.3TB
344AMH17 0021
0MWM
232.8TB
193TB
0MWL
169.7TB
85.2TB
162.1TB
288.5TB
269.2TB
5.5MGOCIPP LINING
121.7TB
37.7TB

Properties (8)

additional_info
SC306736
custom_field_two
3
customer
LACSD
datetime
2017-01-26T15:35:46-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
41152