Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2016, 10:55 AM
  • E 0056_E 0055_20161021_051022.mp4

Date
10/21/2016
W/O
597393
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00028
PipeID
P11285
Time
3:55 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3860
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
V
Project
WO_597393_TV01124_OCT2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
E 0055
Downstream MH
E 0056
Dir. of Survey
Upstream
Length Surveyed
181 ft.
Total Length
181 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
108
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
113
Pipe schematic from manhole E 0055 to E 0056
MH: E 0055MH: E 0056upstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. OBN - Obstacles Construction Debris, 20 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE0 ft. MGO - General Observation - Magnesium hydroxide coating finish0 ft. MSA - Survey Abandoned - 25% DEBRIS FINISH REVERSAL133.3 ft. OBN - Obstacles Construction Debris, 10 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE179 ft. MGO - General Observation - Magnesium hydroxide coating start179 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start181 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE181 ft. AMH - Downstream Manhole, Survey Begins - E 0055181 ft. MWL - Water Level, 15 %of cross sectional area181 ft. MGO - Reversal Inspection181 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    181 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (12)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
2MGOMagnesium hydroxide coating start
0AMHE 0055
181SAP
0MWL
181OBNNOT VISIBLE
0MGO
2SAP
0MWM
181MGOMagnesium hydroxide coating finish
47.7OBNNOT VISIBLE
181MSA25% DEBRIS FINISH REVERSAL

Properties (6)

additional_info
SC301939
custom_field_two
4
customer
LACSD
datetime
2016-10-21T03:55:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false