Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 28, 2016, 07:55 AM
  • E 0027_E 0026_20161028_014555.mp4

Date
10/28/2016
W/O
597393
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00028
PipeID
P07610
Time
12:55 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3867
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
WO_597393_TV01124_OCT2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
E 0027
Downstream MH
E 0026
Dir. of Survey
Downstream
Length Surveyed
411.8 ft.
Total Length
411.8 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole E 0027 to E 0026
MH: E 0027MH: E 0026downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 00270 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES IN MH0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAGNESIUM COATING START2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start358.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish373.5 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES405.2 ft. MGO - General Observation - MAGNESIUM COATING FINISH411.8 ft. MGO - General Observation - ROACHES IN MH411.8 ft. AMH - Downstream Manhole, Survey Ends - E 0026

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    358.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

    373.5 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMHE 0027
0MWM
2MGOMAGNESIUM COATING START
0MGOROACHES IN MH
0MWL
358.4SAP
411.8MGOROACHES IN MH
411.8AMHE 0026
2SAP
373.5SAV
405.2MGOMAGNESIUM COATING FINISH

Properties (6)

additional_info
SC301947
custom_field_two
4
customer
LACSD
datetime
2016-10-28T00:55:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false