Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2016, 10:46 AM
  • 02 1796_02 1795_10102016_034808.mp4

Date
10/10/2016
W/O
596913
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00292
PipeID
P04141
Time
3:46 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3426
Sewer Name
02 MONTEREY PARK RELIEF TRUNK
City
MONEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_596913_TV02215_OCT2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1796
Downstream MH
02 1795
Dir. of Survey
Downstream
Length Surveyed
285.3 ft.
Total Length
285.3 ft.
Structural Index
3
Structural Quick
4I3J
Structural Rating
360
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
360
Pipe schematic from manhole 02 1796 to 02 1795
MH: 02 1796MH: 02 1795downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17961.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"38.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"42.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES47.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"48.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"83.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"124 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"125.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"167.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"170.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"209.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"215.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"233.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"245.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"283.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish283.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1795

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    42.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
283.3FM
0MWL
48.3FM
285.3AMH02 1795
1.6SAV
42.7FM
7.6TF
233.6TF
170.1TF
83.2TF
0MWM
0AMH02 1796
283.3SAV
124TF
125.8TF
215.3TF
167.2TF
38.1TF
209.4TF
61.9TF
245.5TF
47.3TF

Properties (6)

additional_info
SC303460
custom_field_two
2
customer
LACSD
datetime
2016-10-10T03:46:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false