Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2017, 03:57 PM
  • 19 0090_19 0089_842017_120714.mp4

Date
08/04/2017
W/O
0640938
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00722
PipeID
P15282
Time
8:57 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7481
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
LAKEWOOD
Loc. details
Yard
Location Code
Y
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170804SHO_EAST_ARTESIA_TRUNK_SECTS_1235
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0090
Downstream MH
19 0089
Dir. of Survey
Downstream
Length Surveyed
173.3 ft.
Total Length
173.3 ft.
Structural Index
5
Structural Quick
5B31
Structural Rating
73
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
77
Pipe schematic from manhole 19 0090 to 19 0089
MH: 19 0090MH: 19 0089downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12053 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO46.6 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO62.7 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO78.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO88.4 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO94.1 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO97.2 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO102.7 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO106.9 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO113.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO131.7 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO138.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start148.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish160.6 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO170.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish173.3 ft. AMH - Downstream Manhole, Survey Ends - 1230173.3 ft. MGO - General Observation - ACTIVE CONN. @ 3 IN THE MH

Observation photos (14)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    14.2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    46.6 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    62.7 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    78.6 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    88.4 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    97.2 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

    102.7 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    106.9 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    113.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    131.7 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    138.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO

    160.6 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO

Observations (22)

DistanceCodeObservation
102.7SRV
131.7SRV
88.4SRV
138.5SRV
97.2SRV
173.3AMH1230
3SRC
62.7SRV
94.1SRV
113.8SRV
46.6SRV
160.6SRV
0MWL
106.9SRV
170.8SAV
14.2SRV
0MWM
78.6SRV
0AMH1205
3SAV
148.8SRV
173.3MGOACTIVE CONN. @ 3 IN THE MH

Properties (6)

custom_field_three
VISIBLE REBAR AND AGGREGATE
custom_field_two
2
customer
LACSD
datetime
2017-08-04T08:57:34-07:00
documentation
OBREGON, IGNACIO, BRAR
is_lateral_inspection
false