Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2016, 11:16 AM
  • 18 0495_18 0494_20160112_035909_.mp4

Date
01/12/2016
W/O
547025
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00691
PipeID
P14349
Time
3:16 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3034
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_547025_TV18099_JAN2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0495
Downstream MH
18 0494
Dir. of Survey
Downstream
Length Surveyed
623.3 ft.
Total Length
623.3 ft.
Structural Index
2
Structural Quick
413B
Structural Rating
93
O&M Index
2
O&M Quick
312X
O&M Rating
258
Overall Index
2
Overall Quick
Overall Rating
351
Pipe schematic from manhole 18 0495 to 18 0494
MH: 18 0495MH: 18 0494downstream0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 04950 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK ACTIVE0 ft. VC - Vermin Cockroach2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.3 ft. RPZ - Repair Other, within 8 inches of joint: YES - BROKEN PIPE W/ REPAIR49.9 ft. CC - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES67.7 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES68.6 ft. H - Hole, at 02 o'clock, within 8 inches of joint: YES - HOLE W/ POSSIBLE REPAIR?90 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES115.4 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES145.9 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES152.7 ft. MMC - Material Change, Reinforced concrete pipe156 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start156 ft. MMC - Material Change, Vitrified clay pipe174 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES204.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish227.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start240.4 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES261.1 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES272.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish275.8 ft. TBD - Tap Break-In Defective, at 09 o'clock, -, , within 8 inches of joint: YES, 4" - BROKEN INSIDE276.7 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES279.4 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES, Start284.7 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish284.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start305.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish369.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start380 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES, Start380 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish419.4 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish430.6 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start431.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"443.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"466.6 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish501.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start566.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish566.5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start612.4 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish619.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish623.3 ft. VC - Vermin Cockroach623.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0495

Observation photos (16)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - BROKEN PIPE W/ REPAIR

    18.3 ft. - Repair Other, within 8 inches of joint: YES - BROKEN PIPE W/ REPAIR

  • Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

    49.9 ft. - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    67.7 ft. - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Hole, at 02 o'clock, within 8 inches of joint: YES - HOLE W/ POSSIBLE REPAIR?

    68.6 ft. - Hole, at 02 o'clock, within 8 inches of joint: YES - HOLE W/ POSSIBLE REPAIR?

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    90 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    145.9 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Material Change, Reinforced concrete pipe

    152.7 ft. - Material Change, Reinforced concrete pipe

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    156 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    227.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    284.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    369.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

    380 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    430.6 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    501.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    566.5 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (44)

DistanceCodeObservation
204.7FL
443.1TBA
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
152.7MMC
623.3VC
272.2CL
419.4CM
380CM
67.7FM
0AMH18 0495
156FL
369.9CL
275.8TBDBROKEN INSIDE
115.4RFJ
156MMC
430.6CM
284.8CL
501.8CL
284.7RFJ
2.6DAGS
18.3RPZBROKEN PIPE W/ REPAIR
612.4CM
227.4CL
276.7RFJ
0MWM
0MWL
174RFJ
431.6TB
68.6HHOLE W/ POSSIBLE REPAIR?
623.3AMH18 0495
0MGOLATERAL AT MH 3 O'CLOCK ACTIVE
566.4CL
49.9CC
619.2DAGS
566.5CM
380CL
466.6CM
305.5CL
145.9CC
0VC
90CM
240.4RFJ
279.4RFJ
261.1RFJ

Properties (6)

additional_info
SC224628
custom_field_two
2
customer
LACSD
datetime
2016-01-12T03:16:49-08:00
documentation
PRO PIPE
is_lateral_inspection
false