Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2016, 06:36 AM
  • 01 1516_01 1084_20160127_223815.mp4

Date
01/27/2016
W/O
552639
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00210
PipeID
P01934
Time
10:36 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3129
Sewer Name
01 HUNTINGTON PARK TRUNK
City
SOUTH GATE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_552639_TV01246_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
24 in.
Upstream MH
01 1516
Downstream MH
01 1084
Dir. of Survey
Downstream
Length Surveyed
365.8 ft.
Total Length
365.8 ft.
Structural Index
3
Structural Quick
3J25
Structural Rating
181
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
184
Pipe schematic from manhole 01 1516 to 01 1084
MH: 01 1516MH: 01 1084downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 15161 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: NO2 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES11.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish88.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start106.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish136.4 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES150.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start363.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish365.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1084

Observation photos (4)

  • Deposits Attached Grease, 15 %of cross sectional area, from 08 to 09 o'clock,  , within 8 inches of joint: NO

    1 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: NO

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    136.4 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
69.1CM
363.8CM
0MGOLATERAL AT MH 9 OCLOCK
2CM
136.4CM
0MWL
0MGOLATERAL AT MH 3 OCLOCK
0MWM
88.8CL
0AMH01 1516
365.8AMH01 1084
1DAGS
4CL
11.5CM
106.8CL
150.6CM

Properties (6)

additional_info
SC225516
custom_field_two
3
customer
LACSD
datetime
2016-01-27T22:36:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false